Configuration Manual
Release R210

Table of Contents

Other manuals for Honeywell CIU 888

Questions and Answers

  • O
    oblackSep 13, 2025
    Why are flexconn commands not working after NOVRam reset on Honeywell Gateway?
    • A
      Anthony West MDSep 13, 2025
      After a NOVRam reset, if the flexconn commands are not working for a particular flexline radar gauge, it means that the FlexConn address is wrongly configured for radar gauges in CIU 888. To resolve this: 1. Change the flexconn address using SmartView. 2. If the configuration has 8xx gauge type, change the gauge type to 990 and assign a non-used flexconn address. Then, revert the gauge type back to 8xx gauge type.
  • T
    Tracy SmithAug 25, 2025
    Why I am unable to perform manual switchover via Entis Pro on Honeywell Gateway?
    • L
      Lisa ArmstrongAug 25, 2025
      If you are unable to perform a manual switchover via Entis Pro, there are a couple of potential causes: * The Sync Link cable between the CIU 888s might be disconnected. In this case, reconnect the Sync Link cable, wait for the initial synchronization to complete, and check the CIU 888 Web interface for an event log indicating that the system is ready for switchover. Then, try the manual switchover again via Entis Pro. * The CIU 888s in the redundant system setup might not be fully synchronized. Try restarting the secondary CIU 888.
  • S
    Scott MitchellAug 25, 2025
    How to fix 'Active session exists' message when uploading site configuration to Honeywell Gateway CIU 888?
    • A
      Alicia AllenAug 26, 2025
      If you receive an “Active session exists” message when uploading a site configuration to CIU 888 using the Service tool or Migration tool, it means that you are already logged on to CIU 888. To resolve this, close any existing session with CIU 888 before uploading the site configuration again.
  • S
    srogersNov 26, 2025
    Why does the Entis Pro Tank Detail window display a blank screen for Honeywell Gateway?
    • F
      francisco61Nov 26, 2025
      If the Entis Pro Tank Detail window is displaying nothing (blank), here are some possible causes and solutions: * The INI files may not have been updated. Update the INI files using the Migration tool. Then, reload the INI files in Entis Pro using the Entis Pro CIU+ Links application. * There may be a mismatch between Tank and CIU 888 CRCs within CIU 888 due to database corruption, which can be observed in the Logs window of the CIU 888 Web interface with a red ring of light. Perform a Reset to Factory Settings operation via the CIU 888 display and upload a new site configuration to CIU 888 using the Service tool/ Migration tool. * Entis Pro may not be functioning properly. Try shutting down and restarting Entis Pro. Alternatively, shut down Entis Pro, replace the Entis Pro default ...
  • S
    Scott JonesSep 14, 2025
    Why is there a diagnostics difference in LCD and Web Interface for TRL/2 Field port on Honeywell Gateway?
    • D
      Dylan CookSep 14, 2025
      If there's a diagnostics difference in the LCD and Web Interface for the TRL/2 Field port, it indicates improper configuration of TRL/2 data input. Check that the device slave ID is configured correctly in the TRL/2 data input under the Field port and configure it properly.
  • H
    Heidi LynnSep 23, 2025
    How to delete a tank in Honeywell Gateway Service tool?
    • O
      Oscar MoralesSep 23, 2025
      To delete a tank: 1. Change the protocol type back to Modbus RTU. 2. Change the Modbus mapping to user specified. 3. Remove the tank which needs to be deleted from the Service tool and add it to the available list in the user-defined Modbus map. 4. Delete the tank from the Service tool.
  • N
    Nancy DukeSep 7, 2025
    Why doesn't density dip work with default timeout on Honeywell Gateway?
    • M
      Matthew FarrellSep 7, 2025
      If the density dip is not working when the Field port has the default timeout configured (250ms), it's because the density dip command is being aborted due to timeouts on the 1200 baud rate BPM lines. To resolve this, increase the field port timeout to 300-350 ms.
  • H
    Holly BanksSep 8, 2025
    What to do if Change Password option doesn't appear when resetting Honeywell Gateway?
    • R
      Robert HolmesSep 8, 2025
      If the Change Password option does not appear while resetting the factory settings, this could be due to a power disruption during the factory reset. The factory reset must be re-done, ensuring that the Change Password option is displayed this time.
  • C
    Courtney RaymondSep 23, 2025
    Why are element position values zero in Honeywell Gateway temperature profile record?
    • H
      Henry LawrenceSep 23, 2025
      If, in a temperature profile record, the element Position values are zero in Modbus host for TRL2 990 with VITO, it indicates improper configuration in the gauge. Ensure that the gauge is properly configured.
  • J
    John RiceAug 31, 2025
    Why is the Honeywell Gateway CIU 888 ring of light orange?
    • A
      ahardinAug 31, 2025
      If the CIU System Status or Ring of light is orange, this indicates a warning that the compact flash data free space is less than the required limit (below 300MBs). To resolve this, clear the log files by accessing the CIU 888 web interface (https:// 192.168.1.1), entering your credentials, clicking 'clear logs', and then restarting the CIU 888.

Summary

Chapter 1 Introduction

Chapter 2 Installing CIU 888 Service Tool

Installing CIU 888 Service Tool

Instructions for installing the CIU 888 Service Tool.

Installing CIU 888 Service Tool on the new machine

Detailed steps for installing the service tool on a new machine.

Chapter 3 Getting Started

CIU 888 Web interface

Overview of functionalities and access to the CIU 888 Web interface.

Configuring a site using CIU 888 Service Tool

First step in configuration: creating a site using the Service Tool.

Creating a new site

Procedure for creating a new site configuration in the Service Tool.

Configuring a Field port

Steps for configuring serial, Ethernet, and TRL/2 field ports.

Configuring a Tank

Procedures for configuring tank settings under serial and Ethernet ports.

Configuring a GPU Data Input or Modbus Data Input or TRL;2 Data Input

Adding data inputs for GPU, Modbus, or TRL/2 devices.

Configuring a Host port

Configuration of serial and Ethernet host ports.

Configuring User defined Modbus map

Creating and managing user-defined Modbus maps.

Configuring Ethernet Host port

Steps for configuring FTE A, FTE B, and LAN ports.

Configuring Modbus map for TCP;IP ports

Creating, deleting, and editing TCP/IP Modbus maps.

Sending Configuration to CIU 888

Process for sending site configuration to the CIU 888.

Generating INI Files

Steps to generate INI files for Entis Pro.

Verifying Configuration

Procedure to verify the current configuration of the CIU 888.

Chapter 4 Commissioning of a Standalone System Setup

Running the initial setup of the CIU 888

Performing the initial setup and login for the CIU 888.

Logging on to the CIU 888 and changing the initial password

Procedure for initial login and password change on CIU 888.

Verifying the CIU 888 license

Steps to verify if the CIU 888 license is installed and valid.

OPCUA Self-Signed Certificate Management

Managing self-signed certificates for OPCUA communication.

OPCUA CA-Signed Certificate Management

Managing CA-signed certificates for OPCUA communication.

Chapter 5 Commissioning of a Redundant System Setup

Running the initial setup of the primary CIU 888

Performing initial setup for the primary CIU 888 in a redundant system.

Setting up the site configuration

Setting up site configuration for primary CIU 888.

Sending the site configuration to the primary CIU 888

Sending the configured site setup to the primary CIU 888.

Commissioning of the secondary CIU 888

Configuring the secondary CIU 888 as a counterpart.

Chapter 6 Updating CIU 888 Site Configuration

Implementing the required changes in the site configuration

Steps to implement changes in the site configuration.

Sending the site configuration to the CIU 888

Sending updated site configuration to CIU 888.

Special Operating Procedure to perform configuration updates on redundant CIU

Procedure for updating configuration on redundant CIU without restart.

Chapter 7 General CIU 888 Functions

(Re)starting and shutting down the CIU 888

Procedures for starting, restarting, and shutting down the CIU 888.

Appendix A Data Handling

Appendix B Scanning

Appendix C Redundancy

Redundant CIU 888-Experion PKS Integration

Configuration steps for integrating redundant CIU 888 with Experion PKS.

Configuring Experion PKS

Steps for required Experion PKS configuration using Quick Builder.

Appendix H Creation of new Modbus field device; TRL;2 Field Device Configuration File