How to solve “CIU 888 should be configured before updating INI files” message on Honeywell Gateway?
- TtaylorhodgesAug 31, 2025
If you receive the message “CIU 888 should be configured before updating INI files” when updating INI files using the Service tool or Migration tool, it indicates that the CIU 888 has not been fully configured and may be in a factory reset condition. To resolve this, re-upload the site configuration to CIU 888 using the Migration tool, and then update the INI files using the Migration tool.