Why does Honeywell Gateway CIU 888 status switch in Entis Pro after adding a new tank?
- AAngel WilsonSep 3, 2025
When a new tank has been added during an update of the site configuration and the CIU 888 status switches continuously between normal and striked out in the Hot Standby status of Entis Pro, it is because the new tank information is not linked to the host port. To resolve this, on the CIU Prime tab of the Link window in Ensite Pro, remove the CIU Plus to CIU Prime link, click Apply, and then relink again. After that, update the new site configuration to CIU 888 using the Migration tool.