Why are level and pressure values scaled up incorrectly from Honeywell Gateway CIU 888?
- Bbrent07Sep 2, 2025
If the level value in mm and pressure value in Kgf/cm2 are scaled up and shown incorrectly from CIU 888, it indicates that the Modbus scaling factor for these parameters was increased during database configuration. To fix this, reset the scaling factors for these entities on the host ports using Ensite Pro.