Appendix C - Redundancy
Part No.: 4417584_Rev12 Configuration Manual
CIU 888 C - 29
$*6
(SWITCHOVERCOMMAND.OP=ON) is issued to CIU 888 so that the CIU 888
becomes ACTIVE.
For the Write Coil for giving Switchover command to CIU 888 to make
ACTIVE in-case of PASSIVE state, a SWITCHOVERCOMMAND.OP is
created which is associated to OUTPUT controller. The PV Source
Address is given as OUTPUT 1 which needs to configured in control tab
of the point for write.
C.12.4 Configure Points for CIU 888 parameters:
Configure the required points for CIU 888 parameters in Experion PKS.
For example, for Product Level (PL) which is a holding register, under
points in Quick Builder > Add Item>Item Type- Analog point is created
with name "PL". This is associated to the ANALOG controller and the
address format is selected based on EPKS standard format (eg: for 32
signed integer the address format is S32BB, so the PV Source Address