CLASS 320 METER
62-0397-02 8
Temperature Range -20C to +50C
Relative Humidity
Range
0-95% non-condensing
Altitude 2000 meters maximum
Voltage Overload +25% continuously: +100% For 20 cycles
Current Sensor
Overload
100% for 1 minute
Pollution Degree Degree 2 in accordance with IEC 664
Standards
EN 61326-1:2006 IEC 61010-1:2001, 2nd Edition
Installation
(Overvoltage)
Category
Category III
Measurement
Category
Category III
Enclosure Material Type 1 JIC steel or Type 4X Rain Tight
Display Readout LCD
Standard Ranges
2-Wire Delta 120 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 120/208 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 120/240 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 277/480 VAC: 100, 200, 400, 800,1600, 3200 Amp
2-Wire Wye 277 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 400 VAC: 100, 200, 400, 800,1600, 3200 Amp
3-Wire Delta 480 VAC: 100, 200, 400, 800,1600, 3200 Amp
4-Wire Wye 600 VAC: 100, 200, 400, 800,1600, 3200 Amp
RS-485 Serial
Communications
Cable
Cable: UL-listed/rated/3-conductor,
300 VAC, stranded
conductors, 22-26 AWG.
Input/output Voltage: Ground-isolated +/-5.4Vdc
Cable Connector: Screw terminal termination
Circuit Input Isolation: 5.3kVAC
Max Cable Distance: 4000 feet
Max Network Nodes: 64 cabling nodes (including
master)
Baud Rate: 9600, 19200, 38400, 76800
Recommended
In-Line Fuse
Manufacturer: Littlefuse
Mfg. Part No: KLDR.100
Rating: 100mA, time-delay, 600VAC
cartridge fuse