To set a controller as an OPC UA server
1. From the Home Page, click Configure Ethernet Ports and select
ETH1 or ETH2.
2. Under Network Setting, select Use the following IP address and enter
the details in the IP Address, Subnet Mask and Gateway fields.
3. Under Protocol Binding, select OPC UA Server for the Ethernet port.
4. Click Save to save the configuration, and click Back to return to the
Home Page.
5. Click Make to compile the configuration to the controller.
Publishing to Experion
This function enables the user to publish the related configuration for
Experion to configure point and system status for ControlEdge 900
controller in Experion.
For how to publish the configuration to Experion, See "Publishing to
Experion" on page110 for more information.
Configuring DNP3 Slave
DNP3 is used for communication between the controller and a DNP3
master such as a SCADA system like Experion. The controller acts as a
DNP3 slave.
Binding protocol to Ethernet ports
1. From the Home Page of ControlEdge Builder, click the arrow
beside Configure Ethernet Ports, and select ETH1 or ETH2.
2. Under Network Setting, select Use the following IP address and enter
the IP address of the Ethernet port.
3. Under Protocol Binding, select DNP3.
4. Click Save to complete the configuration.
Configuring DNP3 slave protocol
This section only introduces simple procedures to configure DNP3
slave. For more information, see "Configuring DNP3 slave" in the
ControlEgde Builder User's Guide.