ENS7003R0 KO06 2010 
Mains input: Supply voltage 
220 to 240Vac -15% +10% 50/60Hz or 
110 to 120Vac -15% +10% 50/60Hz 
Allowable ambient Temperature & Humidity 
-10 °C; +60°C 
90% RH max. at 40°C (non condensing) 
Approvals 
CE certification to standard EN298:2003 
CE certification to standard EN230:2005 
 
Additional approvals: 
Lloyds (planned) 
EN746-2 compliant 
PED (planned) 
SIL2 (planned) 
Apave (planned) 
Power consumption 
9VA 
Protection class 
IP40 
Vibration   
0.5G 
Mounting 
Plug-in mounting method using sub-base 
Dimensions       
103mm x 103mm x 124mm (W x D x H) incl. sub base. 
Status indicator LEDs   
- Standby 
- Purge 
- Ignition 
- Pilot 
- Main 
- Modulate 
- Flame On 
- Alarm 
The LEDs will shortly blink as soon as power is applied to 
the DBC2000E and then as soon there is a heat demand , 
indicate the burner sequence. 
The LED’s are also used to indicate faults. For example, if 
a loss of flame signal occurs during RUN, the LED’s for 
Alarm, Flame and Main will blink the fault code. 
Reset switch       
When the DBC2000 is in lock out condition and the alarm 
LED blinks, press reset button one time to reset the 
DBC2000 and stop the alarm. If the heat demand is still 
present, the DBC2000e will perform the start sequence 
normally if the fault condition has been resolved, 
otherwise the lock out will repeat. 
If during the lock out condition the DBC2000E is 
deenergized and power is reapplied afterwards, the 
DBC2000 will remain in lock out (non-volatile lock out). 
A remote reset push button switch can be connected 
between terminals 15 and 19. The functionality of the 
remote reset is the same as the red push button on the 
front of the device, with one exception:. 
The remote reset may occur only 5 times during 15 
minutes of operation, while the internal reset buton is 
unlimited. 
Remote communication     
- Communication protocol: Profibus or Modbus (future) 
- Availability of: 
 Sequence status 
 Fault information 
 Flame signal strength 
 Remote reset (max 5x per 15mins) 
 Remote heat demand 
- Transmission speed : 9600bps 
- Interface type : RS485 (M+, M-, COM) 
- Address select : 1~99 encoder switch