When full ON/OFF con trol is se lected (i.e. Pro por tional Band 1 is set to 0) and Loop
Alarm is en abled, the Loop Alarm Time pa rame ter de ter mines the du ra tion of the
satu ra tion con di tion af ter which the Loop Alarm will be ac ti vated. It may be
ad justed within the range 1 sec ond to 99minutes 59 sec onds. This pa rame ter is
omit ted from the dis play se quence if ON/OFF con trol is not se lected or Loop Alarm
is dis abled. The de fault set ting is 99:59.
9.4 EXITING CONTROLLER DEFINE MODE
The operator may exit from Controller Define Mode by pressing the MODE key
until the Exit ? prompt appears in the Message Display, then pressing the SET UP
key, which will cause a return to the mode from which entry was made.
NOTE: An auto matic re turn is made if there is no key ac tiv ity in
Con trol ler De fine Mode for five min utes.
9-11