INSTALLATION INSTRUCTIONS
32-00156-03
SIL
3
Capable
Edition 03.20 · 32-00156-03 · EN
APPLICATION
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D are micro-
processor-based integrated burner controls for automatically
fired gas, oil, or combination fuel single burner applications.
They are intended to replace the R4795 and R7795 Primary
Controls. The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D
systems consist of a relay module, subbase, amplifier, and
purge card. Options include: 2-line VFD (see document 65-
0090-6) or 4-line LCD (see document 32-00110-01) Key-
board Display Module, Personal Computer Interface, Data
ControlBus™ Module, remote display mounting, expanded
annunciator and Combustion System Manager® Software.
Functions provided by the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D include automatic burner sequencing, flame
supervision, system status indication, system or self-diagnos-
tics and troubleshooting. The RM7896 provides a postpurge
function.
This document covers the following 7800 Series Relay
Modules:
1000-Series 2000-Series
RM7895A1014 RM7895A2014
RM7895A1048 RM7895A2048
RM7895B1013 RM7895B2013
RM7896A1012 RM7896A2012
RM7895C1020 RM7895C2020
RM7895C1012 RM7895C2012
RM7895D1011 RM7895D2011
RM7896C1010 RM7896C2010
RM7896D1019 RM7896D2019
EC7895A1010 EC7895A2010
EC7895C1000 EC7895C2000
RM7895A,B,C,D/EC7895A,C;
RM7896A,C,D
7800 SERIES Relay Modules
This document provides installation and static checkout in-
structions. Other applicable publications are:
Publication
No.
Product
32-00110 S7800A2142 4-line LCD Keyboard Display
Module Product Data
32-00166 204729A/C KDM NEMA4 Covers for 4-line
LCD KDM
32-00235 R7824, R7847, R7848, R7849, R7861,
R7886 Flame Amplifiers for the 7800
SERIES Product Data
65-0084 Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0090 S7800A Keyboard Display Module Product
Data
65-0091 S7810A Data ControlBus™ Module
Product Data
65-0095 S7820 Remote Reset Module Product Data
65-0097 221729C Dust Cover Packing Instructions
65-0131 221818A Extension Cable Assembly
Product Data
65-0228 S7810B Multi-Drop Switch Module
Product Data
65-0229 7800 SERIES Relay Modules Checkout
and Troubleshooting Product Data.
65-0249 S7810M ModBus Module (For CE ,
Modbus module S7810M1029 only).
65-0295 50023821-001/2 KDM NEMA4 Covers for
classic 2-line VFD KDM
65-0089 ST7800A,C Plug-In Purge Timer
SPECIFICATIONS
Electrical Ratings (See Table 3):
Voltage and Frequency:
RM7895/RM7896: 120 Vac (+10/-15%), 50/60 Hz (±
10%).
EC7895A,C: 220-240 Vac (+10%/-15%), 50/60 Hz
(±10%)
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A Fast Blow, type SC or equiv-
alent.
Question and Answer IconNeed help?

Do you have a question about the Honeywell EC7895C1000 and is the answer not in the manual?

Honeywell EC7895C1000 Specifications

General IconGeneral
Flame Rod InputYes
ApplicationCommercial and industrial burners
Flame Failure Response Time (sec)0.8 to 4
IgnitionIntermittent
Prepurge TimeAdjustable
Voltage120 VAC
Frequency50/60 Hz
ApprovalsUL, CSA
Current Rating10A

Summary

INSTALLATION INSTRUCTIONS

SPECIFICATIONS

SIL 3 CAPABILITY

INSTALLATION

General Installation Precautions

Essential safety warnings, reading instructions, and installer qualifications.

Mounting Wiring Subbase

Instructions for mounting the subbase and connecting wiring.

FINAL WIRING CHECK

Wiring Verification Procedure

Procedures to verify all wiring is correct before powering up the system.

STATIC CHECKOUT

General Checkout Instructions

Step-by-step guide for conducting the static checkout procedure.

MOUNTING AND HOUSING

PRINCIPAL TECHNICAL FEATURES

Safety Shutdown (Lockout) Conditions

Describes conditions that trigger a safety shutdown or lockout.

SEQUENCE OF OPERATION

Pilot Flame Establishing Period (PFEP)

The phase for establishing pilot flame and proving it.

Main Flame Establishing Period (MFEP)

The phase for establishing the main burner flame.

OPERATION MODES

Initiate Sequence

The initial power-up and pre-operational state.

SETTINGS AND ADJUSTMENTS