MS-9600LS Series Manual — P/N 52646:B2  2/12/2010 189
NFPA Standard-Specific Requirements
The following figure illustrates an example of Central Station/Remote Station Reporting using a 
411UD.  The relay contacts from the FACP may be used to trip any dialer UL listed for Central 
Station/Remote Station Reporting Services.
Figure C.2  FACP Connection to 411UD 
Note: The Monitor Module input, which is being used to monitor 
the 411UD Relay #2 Output (programmed for DACT Trouble),  
must be programmed as ‘Trouble’ at FACP.
Channel1
Channel 2
Channel 3
Channel 4 (2.2K ELR)
Relay Output (DACT Trouble)
Monitor Module ELR resistor
FACP
Supervisory Relay
FACP
Alarm Relay
(2.2K ELRs
P/N 27070)
J4 Not Installed
411UD
Monitor Module Circuit Input
SLC Loop
+     - 
FACP
9600411u.wmf
24 VDC 
nonresettable 
power
1 2 3 4 5 6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
1 2 3
Monitor Module*
FACP
Trouble Relay
*If the SLC device does 
not match the one in this 
figure, refer to the SLC 
manual appendix, which 
contains wiring conversion 
charts for type V and type 
H modules.
411UD FACP
Alarm TB2-1 TB1-1
TB2-2 TB1-3
Trouble TB2-3 TB5-2
TB2-4 TB5-3
Supervisory TB2-5 TB5-4
TB2-6 TB5-6
Table C.2  411-UD Connections to FACP