9600udleslayout.wmf
PS2 Keyboard Interface
Flash Memory Load Enable Switch
UP is normal position for switch
DOWN position allows loading of 
factory software upgrades
Connector for Optional 2nd 
Signaling Line Circuit
Connector for Optional 
Onboard DACT-UD
Battery
24 VDC, 26 Amp Hour maximum
(supervised, nonpower-limited)
Auxiliary
Trouble Inputs
#1       2
To disable ground fault detection, 
remove jumper/shunt from JP2.
Remove JP3 jumper to disable the FACP 
battery charger when using external charger.
JP8- Install NACKEY board in proper 
orientation to configure NACs 4 
StyleY or 2 Style Z circuits
Connectors for 4XTMF Option Module
Cut this jumper to enable 
Supervisory relay when 
4XMTF is installed.
Cut this jumper to supervise 
the 4XMTF when installed 
(see J10 & J11)
(*Factory default relay programming 
as shown on circuit board)
circuit number
ELRs 4.7K, 1/2W
NAC #1   NAC #2   NAC #3  NAC #4
Notification Applicance Circuits
Power-limited, supervised circuits
NAC #1, #2, #3, & #4, Style Y (Class B)
3.0 amps max per circuit
JP8 configured for Class B
using NACKEY card
(factory default configuration)
SLC Loop
(Supervised Power-limited)
Refer to the SLC Wring 
Manual for detailed 
information on wiring 
addressable devices for 
Style 4, 6, and 7
TERM
(EIA-485)
to LCD-80F
EIA-232 to printer or 
personal computer
Power-limited
for EDP-listed equipment 
or personal computer with 
FACP Upload/Downlad 
Utility.  50 foot maximum 
within same room.
OR
2 Programmable Relays & 
1 Fixed Trouble Relay
(nonsupervised)
Contact Ratings:
2.0 amps @ 30VDC (resistive)
0.5 amp @ 30 VAC (resistive)
Contacts show in normal condi-
tion (AC power with no alarm, 
trouble, or supervisory activity).  
A fail-safe trouble relay switches 
to the NO position during
trouble conditions and 
under loss all power.
ACN/ANN-BUS
(EIA-485)
to annunciators
(power-limited,
supervised)
Red
White
Green
Black
Alarm*
NO NC C
Trouble   Supervisory*
NO NC C   NO NC C
Notification Appliance Circuits
Special Application Power
Power-limited, supervised circuits
NAC #1 & #2 Sytle Z (Class A)
3.0 amps max per circuit
JP8 configured for Class A
using NACKEY card
(See Style Y illustrated
near right edge of board)
NAC #1   NAC #2 
Special Application Power
DC Power Outputs (24 VDC)
Power-limited, nonsupervised circuits
Supervise with a power supervision 
relay EOLR-1
Nonresettable Power #2 - 24 VDC  
filtered, power-limited, (1.5 amps 
maximum) Supervision required. 
Suitable for powering annunciators.
Nonresettable Power #1 - 24 VDC  
filtered, power-limited, (1.5 amps 
maximum) Supervision required. 
Suitable for powering annunciators.
Resettable Power - 24 VDC  filtered, 
power-limited, (1.5 amps maximum) 
to smoke detectors.
Supervision required. 
Important: Removing Ground 
Fault Disable jumper JP2 voids 
UL/NFPA Style/Class 
identification for circuits.  
Remove jumper JP2 only with 
AHJ (Authority Having 
Jurisdiction) approval
Basic System Connections