36 MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Product Description Accessories
ANN-LED Board Layout and Connection to FACP
Figure 1.13 illustrates the ANN-LED board showing locations of screw terminals for connection to 
the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a 
compatible FACP.  
 Specifications
• Operating Voltage: 24 VDC
• Max. Current:
• Alarm: 75 mA
• Standby: 15 mA
• Relay Contact Ratings
• 2 amps @ 30 VDC (resistive)
• 0.5 amps @ 30 VAC (resistive)
• Operating Temperature: 32
o 
F to 120
o
 F (0
o 
C to 49
o 
C)
• For indoor use in a dry location only
TB1
J1
SW1
JP2
ANN-BUS
1   2   3   4   5   6   7    8
TB3
Figure 1.13  ANN-LED Connection to FACP
FACP
ANN-LED
ANN-BUS/
ACS BUS
+24 VDC
-24 VDC
9600lstoled.wmf
ANN-BUS and power wiring are 
supervised and power-limited
ANN-BUS (ID#) 
Address DIP switch