MS-9600LS Series Manual — P/N 52646:B2  2/12/2010 191
NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP6 on the FACP main circuit board to supervise placement of the 4XTMF 
module.
2. Refer to “4XTMF Transmitter Module Installation” on page 55 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Fire•Lite Alarms, Inc., Instruction Manual for Remote 
Station Receiver Model RS82.
+        -
Polarity Shown is 
Normal Standby
4XTMF Transmitter Module
Cutting TBL Jumper allows the 
reverse polarity circuit to open with 
a system trouble condition if no 
alarm condition exists.
Power-limited
Figure C.4  Remote Station Connection Using 4XTMF Module
+ 
-
(Dummy load with a 4.7K, ¼ watt resistor 
when no connection is made)