Table 1. FSL100 Cable Data 
 
Note: Safety margins should include an allowance for resistance changes due to changes in T ambient over time. I.e. Higher 
temperature = higher resistance, while resistance may increase due to oxidation or loss of ductility over time. 
 
5.2  Cabling Recommendations 
The FSL100 Flame Detector is supplied fitted with a suitable gland. The use of industrial grade, screened and suitably armoured 
field cable is recommended. 
For example, three core copper cable, with screen (90% coverage) and suitable mechanical protection (i.e. insulated steel wire 
armour) to suit M20 gland entry. 
The maximum conductor size for the terminals is 1.5 mm
2 
(16 AWG). 
Ensure the cable gland is installed correctly and fully tightened. All unused cable/conduit entries must be sealed with a suitable 
certified sealing plug. 
 
5.3  Earth (Ground) Regimes 
Please note: 
 
  Controllers should be connected to protective earth (ground) via an isolator switch that cannot disconnect the earth line. 
  Field cable screens should be connected to instrument earth (ground) in the controller only. The other end of the field cable 
screen shall be cut and isolated. 
  Field cable armour / conduit shall be insulated from the cable screening and earthed (grounded). 
  Avoid earth (ground) loops at all times.