EasyManua.ls Logo

Honeywell HON P095NG-HP - Page 19

Honeywell HON P095NG-HP
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 19
AllspecificationsapplytoboththeMPandHPversions.
Imperialsystem:
Weight
lbs(kg)
A
in(mm)
B
in(mm)
C
in(mm)
D
in(mm)
17.6
(8.0)
4.44
(113)
12.99
(330)
4.92
(125)
2.75
(70)
ThefollowingclassificationsapplyasdefinedinEN334:
Outletpressureareapd
range[bar]
AccuracyclassAC Lock‐uppressureclass
SG
Lock‐uppressure
zoneSZ
p
d
<14.5<14.5 psi(1 barto
3 bar)
2.5 10 2.5
p
d
≥43.5 psi(3 bar) 1 2.5 2.5
Design SpecificsetrangeW
ds
Pilotspring
No. Color
MP
7.25–36.25 psi
(0.5–2.5 bar)
850523ST12660 Green
21.75–72.52 psi
(1.5–5.0 bar)
850523ST12670 blue
43.51–159.54 psi
(3.0–11.0 bar)
850523ST12680 red
87.02–217.56 psi
(6.0–15.0 bar)
850523ST12690 Yellow
HP
145.04–507.63psi
(10.0–35.0 bar)
850523ST12680 red
290.08–870.23 psi
(20.0–60.0 bar)
850523ST12690 Yellow
Pilotdimensionsand
weights
AccuracyclassACand
look‐uppressureclass SG
Pilotsprings

Table of Contents