ICON 100 SERIES USER GUIDE 
EN2B-0002UK07 R0404   
16
 
d16 Fan activation delay at controller start-up and defrost-end: This parameter 
sets the time interval that starts at controller start-up or at the end of a defrost cycle, 
during which the fan must remain off in order to not introduce warm and humid air 
into the case or coldroom (only for model ICON-132S & ICON-132SR). At the end of 
this time interval the fan will be activated when the defrost termination  temperature 
drops and reaches the value set in parameter d17. 
 
d17 Fan activation temperature at controller startup and defrost-end: This 
parameter sets the defrost termination temperature value, detected by the defrost-
termination temperature probe, and below which the fan will be activated when the 
time set in parameter d16 ends (only for model ICON-132S & ICON-132SR). 
 
d19 Display Offset: This parameter fixes the positive or negative correction applied 
to the value detected by the temperature probe and the value shown in the display. 
 
d20 Probe Type Selection: 2k NTC and PT1000 probe selection.  
Where 0= PT1000 and 1= 2k NTC. 
 
d22 Unit of measure: This parameter fixes the unit of measure regarding the 
temperature, i.e., 
o
C if d22=0 or 
o
F if d22=1. 
 
d23 Compressor function during a probe failure: This parameter fixes the 
compressor operating mode during a temperature probe failure. If d23=0, the 
compressor is deactivated and remains that way until the failure is repaired. If 
d23=1, the compressor is activated and remains that way until the failure is repaired. 
Whenever a failure occurs, if d23=2, the compressor alternates a time interval set in 
parameter d25, during which it remains deactivated, with a time interval set in 
parameter d24, during which it remains activated and so on. 
 
d24 Compressor ON-time during a probe failure: This parameter sets the time 
interval. That alternates with the time interval set in parameter d25, during which the 
compressor must remain activated during a probe failure and if parameter d23=2. 
 
d25 Compressor OFF-time during a probe failure: This parameter sets the time 
interval, that alternates with the time interval set in parameter d24. During which the 
compressor must remain deactivated during a probe failure and if parameter d23=2. 
 
d26  Defrost control via real-time clock or Genus
®
 network: local defrost control  
for stand-alone controller via real-time clock or remote defrost control for networked 
controller when connected to Genus
®
. 
 
d27  Stub number: number given to identify refrigeration stub from 0…99 when 
connected to, and viewed from, a Genus
®
 network. 
 
d28  Case number: number given to identify refrigeration case from 0…9…A…U  
when connected to, and viewed from, Genus
®
 network. 
 
d29  Connect to Genus
®
 Network: Command which starts / stops network 
connection to a Genus
®
 front end. 
 
d30 Defrost cycle 1 start time: This parameter sets the time for the first defrost 
cycle within a 24 hour period. 
 
d31 Defrost cycle 2 start time: This parameter sets the time for the second defrost 
cycle within a 24 hour period. 
 
d32 Defrost cycle 3 start time: This parameter sets the time for the third defrost 
cycle within a 24 hour period. 
 
d33 Defrost cycle 4 start time: This parameter sets the time for the fourth defrost 
cycle within a 24 hour period. 
 
d34 First defrost cycle after controller startup: This parameter fixes the time 
interval, starting at controller startup, after which the first defrost cycle is activated. If 
d34=0, the first defrost cycle starts 10 minutes after controller startup. If d34=1, the 
first defrost cycle starts after the hours set in d8. 
 
d38 Minimum temperature alarm differential: This parameter sets the 
temperature below the set point (d1) which activates an under-temperature alarm, 
subject to the alarm delay d7.