JADE
™
ECONOMIZER MODULE
15 62-0331—13
SETPOINTS
CONTINUED
ERV OAT SP
d
32ºF 0 to 50 ºF;
increment by 1
Only when AUX1 O = ERV
EXH1 SET 50% 0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 1 is powered
by the economizer.
With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and
Exh1 H is 50%
EXH2 SET 75% 0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 2 is powered
by the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high
speed fan) settings are required. Default for Exh2 L is 80% and
Exh2 H is 75%
SYSTEM
SETUP
INSTALL 01/01/11 Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG ºF ºF or ºC Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT CONV CONV
HP
CONV = conventional.
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller (O or B terminal).
AUX2 IN n/a Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must pro-
gram CONV mode for W. Shutdown is not
available in the two-speed fan mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
FAN SPEED 1 speed 1 speed/
2 speed
Sets economizer controller for operation of 1 speed or 2 speed
supply fan. The controller does not control the fan but positions
the OA and RA dampers to the heating or cooling mode settings.
NOTE: 2-speed fan option also needs Heat (W1) pro-
grammed in AUX 2 In.
FAN CFM 5000cfm 100 to 50000
cfm;
increment by
100
This is the capacity of the fan. The value is found on the label
from the RTU manufacturer. The cfm of the fan is only used with
DCV CAL ENABLE AUO
AUX1 OUT NONE NONE
ERV
EXH2
SYS
• NONE = not configured (output is not used)
• ERV= Energy Recovery Ventilator
d
• EXH2 = second damper position 24 Vac out for second
exhaust fan.
• SYS = use output as an alarm signal
OCC INPUT INPUT or
ALWAYS
When using a setback thermostat with occupancy out (24 Vac),
the 24 Vac is input “INPUT” to the OCC terminal. If no
occupancy output from the thermostat then change program to
“ALWAYS” OR add a jumper from terminal R to OCC terminal.
Table 4. Menu Structure
a
. (Continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes