EasyManua.ls Logo

Honeywell JADE W7220 - Honeywell MS3103 or MS3105 Communicating Actuator and Thermostat EIM

Honeywell JADE W7220
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JADE
ECONOMIZER MODULE
9 62-0331—13
Fig. 7. Economizer with Honeywell MS3103 or MS3105 communicating actuator and thermostat EIM.
M35158
TO THERMOSTAT
STATUS
LEDS
SENSORS
CONV
POWER
HEAT
COOL
FAN
U1
U2
U3
A
EIM
JADE W7220A1000
ON JADE CONTROLLER:
1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING
2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING
3. MAT IS MIXED AIR SENSOR C7250A1001
4. OAT IS TEMPERATURE CHAGEOVER C7250A1001
SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000
5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
OCC
E-GND
AUX1 OUT
AUX2-I
Y1O
Y2O
Y1I
Y2I
C
TRANSFORMER
24
VAC
120
VAC
C
R
R
1
2
3
4
5
KIT WITH PRESTIGE AND EIM
YTHX9421R5051
EIM
THM5421R1013
RELAY
R822N1011
MS3103J1030
COMMUNICATING DCA
1
3
PRESTIGE
THX9421R5013
C
R
1
THE TRANSFORMER NEEDS
TO BE 100VA.
1

Other manuals for Honeywell JADE W7220