Table 5. Damper minimum position settings and readings on checkout menu.
ALARMS(#)
CONTINUED
SYS ALARM n/a n/a When AUX1-O is set to SYS and there is any alarm (e.g., failed
sensors, etc.), the AUX1-O terminal has 24 Vac out.
ACT UNDER V n/a n/a Voltage received by Actuator is below expected range
ACT OVER V n/a n/a Voltage received by Actuator is above expected range
ACT STALLED n/a n/a Actuator stopped before achieving commanded position
FEATURES ADJUSTABLE ONLY BY USE OF THE W7220 PC MOD TOOL
ACT STALL ALARM
SUPPRESSION
Disabled Enabled or
Disabled
If enabled this feature allows the operator to suppress the stall
alarm in a specific range of the actuator stroke.
a
Table 4 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
2
) sensor, then none of the DCV parameters appear.
b
When values are displayed, pressing and holding the or button causes the display to automatically increment.
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In
the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
e
When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vdc.
f
After 10 minutes without a command or mode change, the controller will change to normal operation.
Fan Speed
Demand Control Ventilation
(CO2 Sensor) Setpoints Checkout
1 NO MIN POS VMAX-HS
1NO N/A N/A
2 NO MIN POS H VMAX-HS
2 NO MIN POS L VMAX-LS
1 YES VENT MIN VMIN-HS
1 YES VENT MAX VMAX-HS
2 YES VENT MIN H VMIN-HS
2 YES VENT MAX H VMAX-LS
2 YES VENT MINL N/A
2 YES VENT MAX L N/A
Table 4. Menu Structure
a
. (Continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes