JADE™ ECONOMIZER MODULE
63-2700—01 14
ADVANCED
SETUP
MA LO SET 45ºF 35 to 55 ºF;
increment by 1º
Temp to activate Freeze Protection (close damper and alarm if
temp falls below setup value)
FREEZE POS CLO CLO
MIN
Damper position when freeze protection is active (closed or MIN
POS).
CO2 ZERO 0ppm 0 to 500 ppm;
increment by 10
CO2 ppm level to match CO2 sensor start level.
CO2 SPAN 2000ppm 1000 to 3000 ppm;
increment by 50
CO2 ppm span to match CO2 sensor.
STG3 DLY 2.0h 0 to 4.0 hours or OFF;
increment by 0.5
Delay after stage 2 for cool has been active. Turns on 2nd stage of
cooling when economizer is 1st stage and mechanical cooling is
2nd stage. Allows three stages of cooling, 1 economizer and 2
mechanical.
OFF = no Stage 3 cooling.
INTERSTG DLY 5 min 1 to 9 minutes
increment by 1
Delay between stages 1 and 2 for cool
SD INPUT CLO CLO
OPN
Indicates shutdown signal from space thermostat or unitary
controller. When controller receives 24 Vac input on the SD
terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed for
CLO. All other controls, e.g., fans, etc. will shut off.
DCVCAL ENA MAN MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers. Resets
ventilation based on the RA, OA and MA sensor conditions. See
Product Data sheet 63-2700 for details. Requires all 3 RA, OA and
MA sensors.
CHECKOUT DAMPER VMIN-HS n/a n/a Positions damper to VMIN position
DAMPER VMAX-HS n/a n/a Positions damper to VMAX position
DAMPER OPEN n/a n/a Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make
sure you pause in this mode to allow for exhaust contacts to
energize due to the delay in the system.
DAMPER CLOSE n/a n/a Positions damper to the fully closed position
CONNECT Y1-O n/a n/a Closes the Y1-O relay (Y1-O)
CONNECT Y2-O n/a n/a Closes the Y2-O relay (Y2-O)
CONNECT AUX n/a n/a Energizes the AUX output. If Aux setting is:
• NONE – no action taken
• ERV – 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for ERV
operation.
d
• SYS – 24 Vac out. Issues a system alarm.
ALARMS(_) MA T SENS ERR n/a n/a Alarms display only when they are active. The menu title “ALARMS
(_)” includes the number of active alarms in parenthesis ().
CO2 SENS ERR n/a n/a
OA T SENS ERR n/a n/a
DA ENTHL ERR n/a n/a
SYS ALARM n/a n/a When AUX is set to SYS and there is any alarm (e.g., failed
sensors, etc.), the AUX terminal has 24 Vac out.
NOTE: The alarms listed are examples. Additional alarms display depending on the parameter settings and
configuration.
a
Table 5 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
2
) sensor, then none of the DCV parameters appear.
b
When values are displayed, pressing and holding the or button causes the display to automatically increment.
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized.
In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
Table 5. Menu Structure
a
. (Continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
Notes