JADE™ ECONOMIZER MODULE
63-2700—01 16
To make a parameter or setpoint change:
1. Use the
and buttons to move to the desired menu.
2. Press the
↵ button (Enter) to display to the first
parameter.
3. Use the and buttons to move to the desired
parameter.
4. Press the
↵ button (Enter) to select the parameter and
display its value.
5. Use the
and buttons to change or increase/
decrease the parameter value.
6. Press the
↵ button (Enter) to store the new value for the
parameter.
7. CHANGE STORED displays.
8. Press the
↵ button (Enter) to return to the current menu
parameter.
9. Repeat steps 4 through 8 for each parameter you want
to change.
10. When finished, press the button (MenuUp/Exit) to
return to the previous menu.
11. Repeat the above steps for each of the three menus -
System Setup, Advanced Setup, and Setpoints.
Table 7. Setup and Setpoint Menus.
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment Notes
SYSTEM SETUP INSTALL 01/01/10 Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG ºF ºF or ºC Sets economizer controller in degrees Fahrenheit or
Celsius.
EQUIPMENT CONV CONV
HP(O)
HP(B)
CONV = conventional; enables configuration of
shutdown parameter.
HP(O) = energize heat pump on Cool
HP(B) = energize heat pump on Heat
FAN CFM 5000cfm 100 to 15000 cfm;
increment by 100
This is the capacity of the RTU. The value is found
on the label from the RTU manufacturer.
AUX OUT NONE NONE
ERV
EXH2
SYS
• NONE = not configured (output is not used)
• ERV= Energy Recovery Ventilator
a
• EXH2 = second damper position relay closure
for second exhaust fan.
• SYS = use output as an alarm signal
OCC INPUT INPUT or ALWAYS When using a setback thermostat with occupancy
out (24 Vac), the 24 Vac is input "INPUT" to the OCC
terminal. If no occupancy output from the thermostat
then change program to "ALWAYS" OR ad a jumper
from terminal R to OCC terminal.
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to
YES. LCD will briefly flash YES and change to NO
but all parameters will change to factory default
values.
ADVANCED SETUP MA LO SET 45ºF 35 to 55 ºF;
increment by 1º
Temp to activate Freeze Protection (close damper
and alarm if temp falls below setup value)
FREEZE POS CLO CLO
MIN
Damper position when freeze protection is active
(closed or MIN POS).
CO2 ZERO 0ppm 0 to 500 ppm;
increment by 10
CO2 ppm level to match CO2 sensor start level.
CO2 SPAN 2000ppm 1000 to 3000 ppm;
increment by 50
CO2 ppm span to match CO2 sensor.
STG3 DLY 2.0h 0 to 4.0 hours or OFF;
increment by 0.5
Delay after stage 2 for cool has been active. Turns
on 2nd stage of cooling when economizer is 1st
stage and mechanical cooling is 2nd stage. Allows
three stages of cooling, 1 economizer and 2
mechanical.
OFF = no Stage 3 cooling.