PFU 780 · Edition 02.12l 24
Parameters
4.2.6 UVS check
Parameter 35
An automatic restart of the burner control unit can be
activated every 24 hours via this parameter. The time
starts each time the start-up signal (ϑ) is applied.
Parameter 35 = 0: Unlimited burner operation.
Parameter 35 = 1: An automatic restart is activated
once every 24 hours.
It must be ensured in this case that the program se-
quence started matches the application. This param-
eter may be set in this way only if the burner can restart
as intended in all operating phases.