PFU 780 · Edition 02.12l 27
Parameters
4.3.1 Permanent pilot burner Parameter 16 = 1
Operating mode: Permanent pilot burner
In the “Permanent pilot burner” operating mode, the pi-
lot burner remains in operation until its start-up signal
drops.
If this parameter is activated (P16 = 1), both flames are
controlled independently in the case of pilot and main
burner monitoring.
Operating mode: Intermittent pilot burner
Start-up as in the illustration “Permanent pilot burner”
with the difference being that the start-up signal for pi-
lot and main burners is applied synchronously and that
immediately after the flame proving period t
FS1
, the
main burner is started.
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2