BCU 480 · Edition 03.16l 21
Function
3.3.2 BCSoft
The Windows software BCSoft allows extended access
to individual statistics, protocol functions, line record-
ers and the parameterization of the burner control unit
via an optical interface. Unit parameters which are not
relevant to safety can be set and adjusted to the spe-
cific application.
3.3.3 Configuration, MasterSlave procedure
PROFIBUS DP is structured as a MasterSlave system.
This allows mono-master or multi-master systems to be
implemented.
A distinction is made between three device types:
DP Masters Class 1 (DPM1)
DPM1 devices are central controllers which exchange
data with the distributed stations (slaves) on the ba-
sis of a defined cycle. This includes, for instance, the
PLC, PC, CNC or VME systems with which the PROFI
BUS DP is operated.
DP Masters Class 2 (DPM2)
DPM2 devices are programming, project planning or
operator-control devices. They are used for configu-
ration and commissioning of the system or for system
operation and visualization in ongoing operation.
DP Slaves
The devices which transmit input information from
the periphery to the master and which issue output
information from the master to the periphery are re-
ferred to as “slaves”.
This also includes the BCU..B1.
3.3.4 Addressing
A maximum of 126 units (masters and slaves) can be
connected to a PROFIBUS DP system. Each station is
assigned an individual PROFIBUS address which can
be set between 0 and 126 using two code switches on
the BCU..B1 board.