BCU 480 · Edition 03.16l 38
Parameters
4.4 Behaviour in start-up position/standby
4.4.1 Flame simulation check in start-up position/
standby
Parameter 15
This defines the instant for the flame simulation check.
t
LV
88
00
t
4
5
1
7
9
18-19
12
V1
14 V2
16-17
01
ϑ
1
If the BCU notices an extraneous signal during the flame
simulation check, it starts the flame simulation delay time
t
LV
(25 s). If the extraneous signal is discontinued dur-
ing this period, the burner can start up. Otherwise, a fault
lock-out occurs.
1
blinks on the display if an extraneous
signal is detected by the pilot burner and
5
blinks if an
extraneous signal is detected by the main burner.
Parameter 15 = 0: The flame simulation check is conduct-
ed after applying the start-up signal (ϑ) during the waiting
time t
W
.
Parameter 15 = 1: The flame simulation check is con-
ducted provided no start-up signal (ϑ) is applied (during
the so-called start-up position/standby). This allows fast
start-up of the burner since there is no waiting time t
W
.
The burner must have been switched off for at least 4 s be-
fore start-up in order for the flame simulation check to be
conducted correctly.
Flame simulation check depending on parameter 16, see
page 37 (Permanent pilot burner) and (Interrupted pilot
burner):
Parameter 15 = 1, parameter 16 = 1
t
ϑ1
ϑ2
88 00 02 06
V1
V2
Parameter 15 = 0, parameter 16 = 1
t
ϑ1
ϑ2
88 00 01 05
V1
V2
02
06
t
W1
t
W2
Parameter 15 = 1, parameter 16 = 0
t
ϑ1
ϑ2
88 00 02 06
V1
V2
Parameter 15 = 0, parameter 16 = 0
t
W1
t
W2
t
ϑ1
ϑ2
88 00 01 05
V1
V2
02
06