BCU 480 · Edition 03.16l 43
Parameters
Main burner
Parameter 11
This indicates the number of possible start-up attempts 
of the main burner.
In accordance with EN 7462, three start-ups are per-
mitted in specific cases if the safety of the installation 
is not impaired (note the requirements of the Stand-
ards).
If no flame is detected during start-up, either a fault 
lock-out occurs or up to two further start-up attempts 
occur. The required functions and, if applicable, the 
number of start-up attempts must be specified when 
ordering.
1 start-up attempt
Parameter 11 = 1
t
SA1 
t
Z 
04  06 02  03 00 
t 
t
FS1 
t
SA2 
9 
12 
V1 
1 
14 
V2 
2 
2 
16-17 
1 
24 
21 
06 
88 
4 
5 
1 
7 
18-19 
28-29 
ϑ
1 
ϑ
2 
If no flame forms during the start-up of the main burner, 
a fault lock-out is performed after expiry of time t
SA2
. 
The display blinks and shows the cause of the fault.
2 or 3 start-up attempts
Parameter 11 = 2, 3
t
SA2 
t
SA2 
t
SA2 
t
SA1 
t
Z 
04  06 02  03 00 
t 
t
FS1 
9 
12 
V1 
1 
14 
V2 
2 
2 
16-17 
1 
24 
21 
06 
88 
4 
5 
1 
7 
18-19 
28-29 
t
W 
06 
06 
05 
05 
t
W 
ϑ
1 
ϑ
2 
If several start-up attempts are set at the works and if 
the BCU does not detect a flame signal during start-
up, it closes valve V2 after the safety time t
SA2
 has 
expired and attempts to start up again. After the last 
programmed start-up attempt has been completed, the 
burner control unit conducts a fault lock-out. The dis-
play blinks and shows the cause of the fault.