Page 2 of 2 DOC-02-039 Rev. A
© 2009 by Honeywell International Inc. All rights reserved.
Unauthorised use of this document is strictly prohibited.
This document is not intended for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specic applications or anticipate all requirements.
All specications are subject to change without notice.
For more information contact your nearest Notier Sales Oce or Distributor
www.notier.com.au
Specications
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 230 μA direct poll; 255 μA group poll.
EOL Value: Not used.
Temperature range: 0°C to 49°C.
Humidity range: 10% to 93% non-condensing.
Current Ratings: 3.0 A @ 30 VDC resistive, non-coded.
2.0 A @ 30 VDC resistive, coded.
0.9 A @ 110 VDC resistive, non-coded.
0.9 A @ 125 VDC , resistive, non-coded.
0.5 A @ 30 VDC inductive (L/R = 5 ms), coded.
1.0 A @ 30 VDC inductive (L/R = 2 ms), coded.
0.3 A @ 125 VDC inductve, (PF=0.35), non-
coded.
1.5A @ 25 VDC , inductve, (PF=0.35), non-
coded.
0.7 A @ 70.7 VDC inductve, (PF=0.35), non-
coded.
2.0A @ 25 VDC , inductve, (PF=0.35), non-
coded.
NOTE: Maximum (Speakers): 70.7 V RMS, 50 W
Ordering Information
FG-05-025 FRM-1 Single intelligent relay output module