SPECIFICATIONS
System Capacity
• Intelligent Signaling Line Circuits .............1 expandable to 10
• Intelligent detectors ............................................ 159 per SLC
• Addressable monitor/control modules ................ 159 per SLC
• Programmable software zones................................ over 2000
• ACS annunciators per CPU.........32 address x 64 or 96 points
NOTE: The CPU2-3030AU can support up to 96 annunciator
address points per ACM-24AT/48A.
Electrical Specications
Primary Input Power: NPS-5CHS Fitted: 240vac, 0.8A, 50Hz. NPS-
11CHS Fitted: 240vac, 1.5A, 50Hz. Input Fuse: 2=M205 8.0A, 250vac
Battery:Two 12V Sealed Lead-Acid batteries. Battery charger capacity:
7AH-85AH (CAB650/CAB900 enclosures hold a maximum of two 33AH
batteries)
Currentdraw(Standby/Alarm):
– AFP-3030 (with display): 0.205 A / 0.225 A.
– AFP-3030 (without display): 0.140 A / 0.150 A.
– LCM-320: 0.130 A.
– LEM-320: 0.100 A.
NOTE: See AFP-3030 Manual # DOC-01-031 for a complete current
draw calculation sheet and details of input and output values.
Enclosure Specications
CAB650:650mm(h) x 450mm(w) x 190mm(d)
CAB900:900mm(h) x 450mm(w) x 190mm(d)
CAB650/BB: 250mm(h) x 450mm(w) x 190mm(d)
18U: 887mm(h) x 610mm(w) x 285mm(d)
28U:1330mm(h) x 610mm(w) x 375mm(d)
40U:1865mm(h) x 610mm(w) x 375mm(d)
18U/BB: 443mm(h) x 610mm(w) x 285mm(d)
All cabinets are powder-coated black fine sand. RAL 9005
Temperature and Humidity
This system meets AS requirements for operation at 0 – 49°C and at a
relative humidity 93% ± 2%.
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult system consultant for latest listing status.
• AS7240.2:2004 & AS7240.4:2004.
• AS4428.3:2010
• Activfire certificate # afp-2973