N16 Instruction Manual P/N LS10239-000NF-E:A 04/20/2021 71
Operational Checks Testing/Maintenance
Sealed lead-acid batteries must be replaced within at most 5 years from their date of manufacture. Minimal replacement battery capacity
appears on the control panel marking label. Immediately replace a leaking or damaged battery. Replacement batteries are available from the
manufacturer.
If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or eyes with water for at least 15 minutes. Water and
household baking soda provides a good neutralizing solution for Sulfuric Acid.
If Sulfuric Acid gets into eyes, seek immediate medical attention.
Ensure proper handling of the battery to prevent short circuits.
Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins.
WARNING: SULFURIC ACID
BATTERIES CONTAIN SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND DAMAGE TO
FABRICS.
WARNING: EQUIPMENT DAMAGE
SHORTING THE BATTERY LEADS CAN DAMAGE THE BATTERY, EQUIPMENT, AND COULD CAUSE INJURY TO
PERSONNEL.