46 N16 Instruction Manual P/N LS10239-000NF-E:A 04/20/2021
Programming User Programming Options From the FACP
Exporting diagnostics to a USB flash drive Tap on the EXPORT DIAGNOSTICS touchpoint. A pop up box will appear prompting you to
insert a USB memory drive and then tap
CONTINUE. Diagnostics will be exported onto the USB memory drive. If the user wishes to cancel
exporting of Diagnostics, tap the touchpoint
CANCEL.
3.3.9 Lamp Test
Tap the LAMP TEST touchpoint to turn on all pixels on the screen. This will illuminate the entire screen as well as the AC Power and Off Nor-
mal LED for approximately four seconds. During this time a tone will sound. A black spot on the screen will indicate that a pixel is out.
3.3.10 History
The history feature allows the user to view the panel history as well as the network history. History views may also be filtered.
Sorting and filtering Tap on the FILTER touchpoint. A touchpoint for SEARCH and CLEAR will appear along with a virtual keyboard. Enter a
date under
DATE RANGE to search a specific date range. Type in a keyword in the CONTAINS TEXT section to search the history for particular
text. To clear a search, tap the
CLEAR touchpoint. Tap on the EXCLUDE BACKGROUND ACTIVATIONS check box to select that feature. Tap again
to clear the field.
History will show, and can be filtered, for the follow-
ing:
All Events This displays the entire history buffer,
regardless of event type. The history buffer can dis-
play up to a total of 10,000 events, including alarms.
Alarms Only This displays only the alarm events
stored in the history buffer.
Troubles Only This displays only the trouble events
stored in the history buffer.
Supervisory Only This displays only the supervi-
sory events stored in the history buffer.
Security/Other This displays only security and
events deemed “other” stored in the history buffer.
(i.e. Critical Process, Prealarm CO Alarm, etc.)
Time Date Interval This displays a screen to allow
for the selection of a time period to define the range of
events displayed, as well as specific event type. (i.e.
All Events, Alarms Only, etc.)
Point Range This displays a screen to allow for the
selection of a beginning and an end point that defines the range of events to be displayed.
Exporting History to USB Flash Drives: Tap on the EXPORT HISTORY touchpoint. A pop-up box will appear prompting the user to insert a
USB flash drive and then tap
CONTINUE. The history will be exported onto the USB flash drive. Tap the CANCEL Touchpoint to cancel history
export.
3.3.11 Cybersecurity History
Cybersecurity history events are stored in the panel history. A master level user is the only user level that can access Cybersecurity History.
Items logged in Cybersecurity history are as follows:
• Signing file failed
• Verify file signature failed
• Verify file signature failed-file open
• Verify file signature failed-start
• Verify file signature failed-sign fail
•N16 starting
• N16 shutting down
• N16 shutdown canceled
•
NOTE: The user must be logged in as either a lever 5 or 4 user to export panel history and diagnostic information.
Figure 11 History Search Screen
Reset
Tue 11/03/20
02:38:06PM
Master
SIGNALS
SILENCED
OTHER
DISABLE
TROUBLE
SUPERVISORY
CO ALARM
FIRE ALARM
12
3
4
5
6
7
89 10
11
12
28
29
30 31
2020July
Sun
Mon
Tue
Wed
Thu
Fri
Sat
12
between
MM/dd/yyyy
and
MM/dd/yyyy
SEARCH
CLEAR
History
Menu - > Test/Diagnostics - > History
NOTE: The user must be logged in as either a lever 5 or 4 user to export panel history and diagnostic information.