EasyManuals Logo
Home>Honeywell>Control Panel>Notifier NFS2-640

Honeywell Notifier NFS2-640 Manual

Honeywell Notifier NFS2-640
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
12 Clintonville Road
Northford, CT 06472-1610 USA
800-289-3473 • FAX 203-484-7118
www.notifier.com
NFS2-640
Listing Document
PN 52741LD:H9 5/19/2022 ECN: 16475
For additional documentation on this product, visit notifiermanuals.com. This additional documentation for the NFS2-640 may be used as a reference
only.
1 Installation
Wiring methods used shall be in accordance with Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681.
Wiring methods used shall be in accordance with Standard for Central Station Alarm Services, UL 827.
This product is intended to be installed in accordance with the following:
Follow these guidelines when mounting the product’s backbox:
Backbox should be installed in a dry, indoor location.
It is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27°C/60-80°F and at
a relative humidity of 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F).
Locate the backbox so the top edge is 66 inches (1.6764 m) above the surface of the finished floor.
Access to the cabinet shall be in accordance with NFPA 90, article 110.33.
Allow sufficient clearance around cabinet for door to swing freely.
NOTE: The term NFS2-640 is used to refer to the NFS2-640 and NFS2-640E unless otherwise noted.
NOTE: For Mass Notification applications, Class A circuits called out in this manual are Class X.
NFPA 70 - National Electrical Code NFPA 16 - Standard for Deluge-Foam Water Systems
NFPA 72 - National Fire Alarm Code NFPA 17 - Standard for Dry Chemical Extinguishing Systems
NFPA 12 - Standard on Carbon Dioxide Extinguishing Systems NFPA 17A - Standard for Wet Chemical Extinguishing Systems
NFPA 12A - Standard on Halon 1301 Fire Extinguishing Systems NFPA 2001 - Standard for Clean Agent Fire Extinguishing Systems
NFPA 13 - Standard for Installation of Sprinkler Systems UL 2610 - Standard for Commercial Premises Security Alarm Units
and Systems
Canadian Electrical Code, Part I NFPA 15 - Standard for Water Spray Fixed Systems
ULC S524 - Standard for the Installation of Fire Alarm Systems ULC S561 - Installation and Services for Fire Signal Receiving
Centers and Systems
NFPA 92 - Standard for Smoke-Control Systems ULC-S527-11 - Standard for Control Units for Fire Alarm Systems
NFPA 2010 - Standard for Fixed Aerosol Fire Extinguishing System UL 864 Standard for Control Units and Accessories for Fire Alarm
Systems, 10th Edition
UL 2572 - Standard for Mass Notification Systems
Terminal Block/
Connector
Description Specifications
TB4 Alarm & Trouble Output Relays -
Common
Power-limited (Class 2) only if connected to a power-limited source
Voltage and Current: Rated 2.0 A at 30 VDC resistive
Non-supervised
TB5 Supervisory & Security Output Relay
- Common or programmable
Power-limited (Class 2) only if connected to a power-limited source
Voltage and Current: Rated 2.0 A at 30 VDC resistive
Can be programmed as Alarm via VeriFire Tools
Non-supervised
Table 1 CPU2-640 Wiring Connections (1 of 2)

Other manuals for Honeywell Notifier NFS2-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-640 and is the answer not in the manual?

Honeywell Notifier NFS2-640 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-640
CategoryControl Panel
LanguageEnglish

Related product manuals