NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022 37
BMP-1 Blank Module Plate
BP2-4 Battery Dress Plate
NFS-LBBR Red Battery Box
NFS-LBB Battery Box
CAB-4 Series Doors (Black unless “R” is added to the P/N. Add “B” to the P/N
for blank door)
DR-A4 A-sized door, 1 row of equipment
DR-B4 B-sized door, 2 rows of equipment
DR-C4 C-sized door, 3 rows of equipment
DR-D4 D-sized door, 4 rows of equipment
CAB-4 Series Backboxes (Black unless “R” is added to the P/N.)
SBB-A4 A-sized backbox
SBB-B4 B-sized backbox
SBB-C4 C-sized backbox
SBB-D4 D-sized backbox
CAB-4 Series Trim Rings (Black unless “R” is added to the P/N)
TR-A4 A-sized trim ring
TR-B4 B-sized trim ring
TR-C4 C-sized trim ring
TR-D4 D-sized trim ring
CHS-4L Low-Profile Chassis
CHS-4, CHS-4N Chassis for 4 Option Boards
NFS2-640 Chassis for 1st row
DP-1B Blank Dress Plate
DP-DISP2 Dress Panel: NFS2-640/E in top row
DP-GDIS1 Dress Plate for Row A of the CAB-4 series cabinets
DP-GDIS2 Dress Plate for Rows B-D of the CAB-4 series cabinets
Trim Ring: TR300, TR300-IV
Color Kit: CK300, CK300-IV, CK300-IR, CK300-IR-IV, CK300-BL, CK300-IR-BL
IR Color Kit: CK300-IR, CK300-IR-IV, CK300-IR-BL
Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous Editions of UL 864
NOTE: The products in this list have not received UL 864 9th or 10th Edition certification and may only be used in retrofit applications.
ACM-16AT Annunciator Control Module
ACM-32A Annunciator Control Module
ACPS-2406 Auxiliary Charger/Power Supply
AEM-16AT Annunciator Expander Module
AEM-32A Annunciator Expander Module
AFM-16A Annunciator Fixed Module
AFM-32A Annunciator Fixed Module
AMG-1/E Audio Message Generator
APS-6R Auxiliary Power Supply
B501BH/B501BHT Sounder Base
BGX-101L Addressable Manual Pull Station
CHG-120 Battery Charger
FCPS-24 Field Charger/Power Supply
IPX-751 Advanced Multi-Sensor Intelligent Detector
MMX-1 Addressable Monitor Module
NCA Network Communications Annunciator
PRN-4, PRN-5 80-Column Printers
RFX Wireless Transmitter (version 2.0 and higher)
SDRF-751 Wireless Photo/Thermal Smoke Detector (Not ULC-listed)
VS4095 Keltron Printer (Dress plate P-40) (Not ULC-listed)
XPIQ Quad Intelligent Audio Transponder (NAC Applications)
XP5-C Transponder Control Module
XP5-M Transponder Monitor Module
XPC-8 Transponder Control Module
XPM-8 Transponder Monitor Module
XPM-8L Transponder Monitor Module
XPP-1 Transponder Processor
XPR-8 Transponder Relay Module
Refer to document 15378, Device Compatibility Document, and document 51253, SLC Signaling Line Circuit Manual, for a list of other devices com-
patible with this FACP.
7 System Configuration
The following is the minimum configuration to meet NFPA, UL, and ULC requirements for the categories listed.
Module Description CS Local AUX RS P (PPU) P(Burg) REL P Rec
Process
Mana.
CPU2-640CPU2-640E CPU Board w/ display Y Y Y Y Y Y Y Y Y
KDM-R2 Keyboard Display Module Y(1) Y(1) Y(1) Y(1) Y(1) Y(1) Y(1) Y(1) Y(1)
NCA-2/C
Network Control Annunciator Y(1) Y(1) Y(1) Y(1) Y(1) Y(1) Y(1) Y(1) Y(1)
LEM-320 Loop Expander Module O O O O O O O O O
KAPS-24 (Only 1 needed per unit)
Alternate Construction CPS-24
Power Supply Y Y Y Y Y Y Y Y Y
KAPS-24E (Only 1 needed per
unit)
Alternate Construction CPS-24
Power Supply Y Y Y Y Y Y Y Y Y
FCPS-24S6 Power Supply/Battery Charger O O O O O O O O O
FCPS-24S8 Power Supply/Battery Charger O O O O O O O O O
PSE-6 Power Supply/Battery Charger O O O O O O O O O
PSE-10 Power Supply/Battery Charger O O O O O O O O O
ACPS-610
Alternate Construction CPS-24
Power Supply/Battery Charger O O O O O O O O O
ACPS-610E
Alternate Construction CPS-24
Power Supply/Battery Charger O O O O O O O O O
TM-4 Transmitter Module N N Y Y(2) Y O O O O
DVC/DVC-EM Digital Voice Command/Extended
Memory Module
OO(3)OO O O O O O
DVC-RPU Digital Voice Command Remote Paging
Unit
OO(3)OO O O O O O
DAA-5025 (E) Digital Audio Amplifier O O(3) O O O O O O O
DAA-5070 (E) Digital Audio Amplifier O O(3) O O O O O O O
NCS4-W-ONYX/
NCS4-F-ONYX
Network Control Station O O O O O O O O O
NCS5-W-ONYX/
NCS5-F-ONYX
Network Control Station O O O O O O O O O
Table 12 System Configuration (1 of 3)

Other manuals for Honeywell Notifier NFS2-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-640 and is the answer not in the manual?

Honeywell Notifier NFS2-640 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-640
CategoryControl Panel
LanguageEnglish

Related product manuals