114 NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Operating Instructions Read Status
Pressing 3 for IP Settings while viewing Communicator Screen #1 will display settings for the ethernet por-
tion of the Communicator. The screen will indicate if DHCP has been enabled Yes or disabled No. If the
DHCP has not been enabled, the Static Settings will be displayed.
Communicator Screen #2 allows the programmer to press 1 to view the Primary Communication Path set-
tings or 2 to view the Secondary (backup) Communication Path settings for the Communicator and indi-
cates the Call Limit for Communicator trouble calls within a 24 hour period.
Pressing 1 while viewing Communicator screen #2 will cause the following screen to be displayed:
Pressing 1 for POTS indicates whether the receiver has been enabled or disabled. It also provides information on the receiver such as:
• Account Code
• Phone Number Prefix
• Phone Number
• Communication Format
Pressing 2 for Ethernet indicates whether the receiver has been enabled or disabled. It also provides information on the receiver such as
CS account info.
Pressing 3 for Cellular indicates whether the receiver has been enabled or disabled. It also provides information on the receiver such as
the CS account.
Communicator Screen #3 allows the user to view the Event Codes for the chosen communication format as
well as the Test Time Interval and 24 Hour Test Time.
Communicator Screen #4 allows the user to viewwhether the reporting style is by Point or Zone.
4.23.11 Print
To print program data or control panel status, press 2 while viewing Read Status Screen #5. The following
screens will be displayed:
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail all of the system activities since the
file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail all of the system activations during
walktest since the log was last cleared.
Pressing 3 while viewing Print Screen #1 allows the user to print the Walktest summary which will list the total of each type of input
activation.
Pressing 1 while viewing Print Screen #2 allows the user to print the detector data for each addressable smoke detector connected to the
system. A printout, similar to the following example, will be generated if an optional printer is connected to the FACP.
READ STATUS
INSTALLED YES
2=POTS SETTINGS
3=IP SETTINGS
Communicator Screen #1
COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
TBL REPORT LIMIT 0
Communicator Screen #2
COMMUNICATOR
1=POTS
2=ETHERNET
3=CELLULAR
COMMUNICATOR
1=EVENT CODES
TEST TIME INT 24
24HR TEST TIME 0100
Communicator Screen #3
COMMUNICATOR
REPORT STYLE POINT
Communicator Screen #4
DEVICE # DEVICE TYPE % DRIFT COMP CHAMBER TIME/DATE
1D001 SMOKE (PHOTO) 20 1281 12:01 AM 01-08-2016
1D002 SMOKE (PHOTO) 20 1281 12:01 AM 01-08-2016
1D003 SMOKE (PHOTO) 21 1259 12:01 AM 01-08-2016
1D004 SMOKE (PHOTO) 20 1309 12:02 AM 01-08-2016
1D005 SMOKE (PHOTO) 21 1281 12:02 AM 01-08-2016
1D006 SMOKE (PHOTO) 20 1322 12:02 AM 01-08-2016
1D007 SMOKE (PHOTO) 20 1280 12:02 AM 01-08-2016
1D008 SMOKE (PHOTO) 20 1215 12:02 AM 01-08-2016
READ STATUS
1=FUTURE USE
2=PRINT
3=TIME/DATE
Read Status Screen #5
PRINT
1=HISTORY
2=WALKTEST LOG
3=WALKTEST SUMMARY
PRINT
1=DETECTOR DATA
2=COMM SETTINGS
3=EXIT PRINTING
Print Screen #2
Print Screen #1