10 SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
Section 1: Product Description
The SFP-2402 is a two zone FACP (Fire Alarm Control Panel) and the SFP-2404 is a four zone
FACP. The information in this manual refers to both the SFP-2402 and SFP-2404 unless otherwise
specified. These control panels provide reliable fire signaling protection for small to medium sized
commercial, industrial and institutional buildings. The FACP is compatible with System Sensors
i
3
detectors which are microprocessor-based conventional smoke detectors that can transmit a
maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’
signal when the ambient temperature falls below the detector rating (refer to System Sensors i
3
Installation and Maintenance Instructions document I56-1800-00 for device specifications). In
addition, the control panel is compatible with conventional input devices such as two-wire smoke
detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other
normally-open contact devices. Refer to the Notifier Device Compatibility Document for a
complete listing of compatible devices.
Outputs include one NAC (Notification Appliance Circuit) on the SFP-2402 and two NACs on the
SFP-2404. Each FACP has a Form-C Alarm and Trouble relay and 24 VDC special application
resettable power. In addition, the SFP-2404 has a Form-C Supervisory relay and a nonresettable
special application power output. The FACP supervises wiring, AC voltage and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo
sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify
a remote station or initiate a auxiliary control function. The SFP-2402E and SFP-2404E offer the
same features as the SFP-2402 and SFP-2404 but allows connection to 220/240 VAC.
1.1 Product Features
Style B (Class B) IDC (Initiating Device Circuit)
one zone programmable for combination supervisory and
waterflow
SFP-2402 - two IDCs
SFP-2404 - four IDCs
Style Y (Class B) NAC (Notification Appliance Circuit)
SFP-2402- one NAC
SFP-2404 - two NACs
Form-C Alarm Relay
Form-C Trouble Relay
Form-C Supervisory Relay (SFP-2404 only)
3.0 amps total system current standard for SFP-2402 and SFP-2404
6.0 amps total system current available for SFP-2404 with optional second transformer
Dress Panel DP-3-B
Optional Trim Ring P/N: TR-1-B for semi-flush mounting the cabinet
Control Buttons
ACK (Acknowledge)
Alarm Silence
Reset
NOTE: Unless otherwise specified, the terms SFP-2402 and SFP-2404 are used in this manual
to refer to the SFP-2402 and SFP-2402E as well as the SFP-2404 and SFP-2404E FACPs
respectively.
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
TROUBLE
TROUBLE
TROUBLE
TROUBLE MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCEFIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
AC
POWER
NAC
DISABLE
NAC
FAULT
SYSTEM
TROUBLE
POWER
TROUBLE
WALK
TEST
ALARM
SILENCE
ZONE
DISABLE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
SFP-2404

Table of Contents

Related product manuals