EasyManua.ls Logo

Honeywell Notifier SFP-2404 - Installation of Optional Modules; 1: CAC-4 Class a Converter Module (SFP-2404 Only); Installation; Wiring Nacs and Idcs for Class a

Honeywell Notifier SFP-2404
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24 SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
Installation Installation of Optional Modules
2.6 Installation of Optional Modules
2.6.1 CAC-4 Class A Converter Module (SFP-2404 only)
Installation
The CAC-4 Module can be used to convert the four Style B (Class B) Initiating Device Circuits to
Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class
A). The module plugs into connector J1 which is located at the top right of the SFP-2404 main
circuit board.
Install the three supplied standoffs in the holes on the main circuit board as indicated in the
following figure. Carefully align the connector on the CAC-4 with J1 on the FACP main circuit
board and press the module securely into place. Make certain the pins are properly aligned to
prevent bending or breaking of any connector pins.
Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB2 of the SFP-2404 and TB1 of
the CAC-4 module. Wire the Style D (Class A) Initiating Device Circuits using TB3 of the SFP-
2404 and TB1 of the CAC-4. Make certain to observe polarity when connecting the devices to the
circuits. The B+ and A+ terminals must comprise the feed and return for the positive side of a
device and the B- and A- terminals must comprise the feed and return for the negative side of a
device. To configure any of the zones for Class B when the CAC-4 is installed, simply wire to the
B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistor after the last device
!
CAUTION: DISCONNECT POWER
REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING MODULES OR
WIRING.
Figure 2.10 CAC-4 Module Installation
J1 Connector
SFP-2404 Main Circuit Board
Secure to Standoffs
Secure to Standoff
CAC-4 Module
ms4tocac.wmf

Table of Contents

Related product manuals