SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014 17
Backbox Mounting Installation
When using batteries larger than 7 Amp Hour (up to 18 Amp Hour), the BB-17 battery box (or UL-
listed equivalent) must be installed. To install the BB-17:
1. Mount the FACP cabinet to the wall.
2. Remove knockouts on the bottom of the FACP cabinet and top of the BB-17
3. Using conduit, hang the BB-17 from the FACP cabinet making sure there is at least ½” of
clearance between the two cabinets.
4. Anchor the BB-17 to the wall.
Top
Depth = 2.875” (7.3 cm)
Door = 14.677” (37.28 cm)
Depth = 3.05”
(7.75cm)
Door = 15.342”
(38.97 cm)
Bottom
Battery Box = 8.5”
(21.59 cm)
Battery Box = 14.5”
(37.384 cm)
Depth = 4.75”
(12.065 cm)
Figure 2.2 Backbox and Battery Box