EasyManua.ls Logo

Honeywell Notifier SFP-2404 - Page 27

Honeywell Notifier SFP-2404
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014 27
Installation of Optional Modules Installation
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the FACP. In addition, the System Trouble LED will turn on to
indicate the Disconnect condition.
Figure 2.13 4XTM Transmitter Module
Connect to:
• SFP-2404 Connectors J3 & J5 or J4 & J6
• SFP-2402 Connectors J3 & J5.
Disconnect
Switch
shown in
disconnect
position
TBL Jumper
`Remote Alarm (power-limited)*
`Remote Trouble (power-limited)*
No connection
`Municipal Box (nonpower-
limited)*
1+
2-
3+
4-
5
6+
7-
Polarities are shown for module activation
Note: 4XTM Module is not suitable for transmitting reverse
polarity supervisory signal.
* Wiring from these terminals
can exit the protected premises.
Dummy load terminals 6 and 7
(4.7k:, ¼ watt resistor) if
Municipal Box is not connected.
Disconnect LED
4xtmf.wmf

Table of Contents

Related product manuals