NOVAR ES3.S EXECUTIVE CONTROLLER
31-00366—01 2
INTRODUCTION
The Novar ES3.S functions as an executive control module in Novar Opus Magnum building control supervisor, this Pop-
Off Pop-On design fits into XCM.10S and Savvy base-plate to provide easy migration. This document provides
instructions for installing the Novar ES3.S Executive Controller into an existing base-plate, and checking the installation.
Fig. 1. Novar ES3.S electronics assembly and bottom cover plate are included. XCM.10S and Savvy Base-plate is
currently a piece installed on site and is fully compatible with the new system (separate piece).
PRECAUTIONS
Take the following precautions during installation:
OBSERVE NATIONAL AND LOCAL ELECTRICAL CODES.
Reduce the risk of electrical shock or fire. Do not interconnect the outputs of different Class 2 circuits.
Do not rely on the Novar ES3.S as a final safety device.
Make sure that the 24-VAC power wiring is connected to a dedicated transformer. No other devices (including
the outputs) should be powered by the transformer connected to the Novar ES3.S
Do not ground the transformer for this module on the secondary side.
Make sure that the Novar ES3.S power cannot be switched off accidentally. The Novar ES3.S requires
continuous power for proper operation.
If the Novar ES3.S has been provided as a replacement for an xcm.10S and Savvy Controller, the instructions in
this document for wiring a Digital Outdoor Light Sensor (OLS) and/or an Outdoor Temperature Sensor (OTS) to
the Novar ES3.S must be followed carefully. See “Wiring” on page 4.