Installing the PW-6000 Two-Reader Module
Wiring
PW-6000 Two-Reader Module Installation Guide, Document 800-01951, Revision C 11
Reader Wiring
The following Honeywell reader module numbers have been approved by UL for use with the
PW6K1R2: OM40BHONA, OM55BHONA, OP10HONE, OP30HONE, OP40HONE, OP90HONE,
OT30HONA, OT31HONA, OT35HONA, and OT36HONA.
Each reader port supports a reader with TTL interface. Power to the reader is selectable as 5VDC or
12VDC (pass-through). This selection is done by setting the jumpers J2 for reader 0 and J3 for reader
1. Set jumper at position "5" for 5VDC or "12" for pass-through 12VDC. The factory defaults set J2
and J3 to "5".
For wiring to a reader port:
The LED control terminal in each reader port can be configured via host software to support one-wire
single or bi-colored reader LED. An example of the most common configuration is shown below. If
Beeper Control is not used, its terminal can be programmed to be the second wire for the two-wire
bi-colored reader LED.
To fully utilize each reader port, a 6-conductor cable (18AWG) is required. Reader port configuration
is set via host software.
Table 5: Settings for Wiring to a Reader Port
Terminal Typical Wire Color Wiegand Reader Clock/Data Reader
1 Red Power (5 or 12
Vdc)
Power (5 or 12 Vdc)
2 Brown LED control LED control
3 Yellow Beeper Control Beeper Control
4 White Data 1 Signal Clock Signal
5 Green Data 0 Signal Data Signal
6 Black Common Common
Table 6: Settings for Configuring an LED Control Terminal
LED Output-> High Tri-Stated Low
Single Color LED LED On LED Off LED Off
Bi-Color LED Green LED On Both LEDs Off Red LED On