Installing the PW-6000 Input Module
Specification
Specification
The Input Board is for use in low voltage, class 2 circuits only.
Primary power:
10 to 16VDC 250mA
Relay contacts:
Relays 0 and 1 outputs, Form-C, 2A @ 28VDC, resistive
Inputs:
• 16 supervised, End of Line resistors 1k ohm ± 1% tolerance
• 2 unsupervised dedicated inputs
Wire requirements:
Mechanical:
Environment:
Set Up
Power 1 twisted pair, 18AWG
RS-485
24AWG, 4,000 feet (1,200 m) max., 2-twisted pair with shield (120
Ω,
23pf) (Belden 9842 or equiv.)
Alarm inputs 1 twisted pair per input, 30 ohms max.
Outputs As required for the load
Readers 6 conductors, 18AWG, 500 feet (150m) max. shield and drain
Dimension 5.5" (140mm) W x 9" (229mm) L x 1" (25mm) H
Weight 12 oz. (340g) nominal
Temperature 0°C to +49°C, operating, -55°C to +85°C, storage
Humidity
0% to 85% RHNC
Table 1: PW-6000 Input Module Jumper Settings
Jumper Setting Default Selected
J1 OFF X Port 1 RS-485 EOL
terminator is not active
ON Port 1 RS-485 EOL
terminator is active