Installing the PW-6000 Input Module
LED Operation
PW-6000 Input Module Installation Guide, Document 800-01952, Revision B 5
LED Operation
The Input Board uses two onboard LEDs (D1 and D2) to provide status information
during the power-up sequence as well as during normal operation.
In addition to the status LEDs, there are two additional relay status LEDs and 16 input
status LEDs on board. The input LEDs flash when there is an alarm associated with
the input. When any relay or input is energized or ON, its corresponding status LED
becomes ON also. The LED remains ON for as long as the relay is energized.
Table 3: PW-6000 Input Module Onboard LED Settings
Mode LED D1 LED D2 Description
Power-up
sequence
ON OFF Start power-up, hardware setup.
OFF ON Testing RAM.
ON ON Testing ROM and completing
initialization.
FLASH ON LED D1 flashes four times after
power-up is completed.
Normal
Operation
FLASH
This is the processor heartbeat LED. It
flashes once every second. A short ON
time (~20% duty cycle) indicates the
board is offline or has lost serial
communication with the Controller
board. A long ON time (~80% duty
cycle) indicates the board is online and
communicating with the Controller
board.
FLASH Flash when there is activity on its Serial
Port.