Installing the PW-6000 Input Module
Mounting Options
PW-6000 Input Module Installation Guide, Document 800-01952, Revision B 9
Relay 1 is a general-purpose relay output and is not available when the board is
rack-mounted.
Use sufficiently large gauge of wires for the load current to avoid voltage loss.
Mounting Options
This board can be mounted on-edge in the rack-mount enclosure provided by
Honeywell or it can be mounted flat against any surface using standoffs under the
mounting holes provided in each of the four corners of this board.
When this board is rack-mounted, the connectors for one general-purpose output, two
general-purpose outputs, and two dedicated inputs are not accessible and should not
be used.
The most common reason for mounting a board flat is that it is being installed
remotely to be located near the alarms being monitored. In this case, mount it in its
own enclosure. Use the two dedicated inputs to monitor cabinet tamper and power
fault. The additional general-purpose output provided allows for control of a local
horn or other equipment.
Installing the Module
1. Set Jumpers and DIP switches.
2. Mount this board in the appropriate enclosure. If this board is being mounted
in a rack, the component side of the board is to your right as you face the rack.
3. Connect the communications and power supply to the circuit boards with the
Power Supply Harness.
Warning: DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET UNTIL
ALL WIRING HAS BEEN INSTALLED AND RECHECKED
.
4. Connect wiring to alarm input sensors or install jumper wire as appropriate.
5. Connect relay output wiring as appropriate.
6. Connect communications wiring to the Intelligent Controller.
7. Recheck wiring for correct connections and continuity.
8. When all boards have been installed, connect the power supply cord for proper
connections and power.
9. Set up the panel controls using the host software.