14 www.honeywell.com
PW7K1R1E Wiring and Setup
Factory Default Communication Parameters
2.5 Factory Default Communication Parameters
2.6 Bulk Erase
The bulk erase function can be used for the following purposes:
Erase all configuration, sets MR62e to OEM setting (sanitize board).
Restore to OEM default parameters.
2.7 Bulk Erase Steps
Do not remove power during steps 4-6.
1. Set S1 DIP switches to: 1 & 2 “ON”, 3 & 4 “OFF”.
2. Apply power to the MR62e.
3. Watch for LEDs 1 & 2 and 3 & 4 to alternately flash at a 0.5 second rate.
4. Within 10 seconds from applying power, change switches 1 or 2 to “OFF”. If
these switches are not changed, the MR62e will power up using the OEM
default communication parameters.
5. LEDs 1 and 2 alternately flash at a 0.5 second rate while the memory is being
erased.
6. Once the memory is eased, LED 1 will be on for about 3 seconds, then the
MR62e will reboot.
Table 3: Factory Default Communication Parameters
Network : static IP address: 192.168.0.251
Subnet Mask : 255.255.0.0
Default Gateway :192.168.0.1