R7284U Electronic Oil Primary
Application
The R7284U Electronic Oil Primary is a line voltage, 
safety rated, interrupted and intermittent ignition oil 
primary control for oil fired burners.
The R7284U used with a cad cell flame sensor operates 
the oil burner, spark igniter and oil valve.
Features
User Interface
There are two user interfaces: basic and advanced. 
Both interfaces consist of three buttons: s, t and "i".
The advanced interface has a two-line display used 
to configure device parameters, retrieve diagnostic 
information and display system status.
The basic interface has a single LED used to display 
error codes and system status.
In general, the "i" button cycles through the display 
options and acts as an "enter" key (in set-up modes).
Limited Recycle
This feature limits the number of recycle trials (for each 
call for heat) to a maximum of three trials. If the flame 
is lost three times and does not successfully satisfy a 
call for heat, the R7284 locks out.
Disable Function
Pressing and holding the "i" button will disable all 
control functions until 3 seconds after the button is 
released.
Lockout Modes
The R7284 has three types of lockout modes that are 
entered when an error is encountered.
Disable Function
Pressing and holding the "i" button will disable all 
control functions until 3 seconds after the button is 
released.
Lockout Modes
The R7284 has three types of lockout modes that are 
entered when an error is encountered.
• Soft Lockout: Caused by a temporary internal 
error such as low voltage. The control recovers 
automatically after the error is no longer detected.
• Hard Lockout: Caused by a failure internal to the 
control or by a system fault such as flame out of 
sequence. A Hard Lockout will result in a no heat 
condition. To reset from a Hard Lockout, press and 
hold the "i" button for 2 seconds.
• Restricted Lockout: Caused by a number of con-
secutive hard lockouts on the same heat cycle. To 
reset from a Restricted Lockout, press and hold 
the "i" button for ten seconds. 
Cad Cell Resistance
Cad cell resistance can be checked without using an 
ohm meter.
Basic Interface:
Press and release the "i" button. The resulting flashes 
indicate the resistance. See Table 6.
Advanced Interface:
The cad cell resistance is shown on the display.
Specifications
Timing: 
Valve-on Delay: 0-30 seconds 
Burner Off Delay: 0-8 seconds
Lockout: 15, 30 or 45 seconds 
Recycle: 60 seconds (fixed) 
Ignition Carryover: 10 seconds (fixed)
Electrical Ratings: 
Inputs: 
  Voltage: 102 to 132 Vac. 120 Vac nominal 
  Current: 0.5A plus burner motor, valve and  
    igniter loads. 
  Frequency: 60 HZ
Outputs: 
Relay Contacts: 
  Burner: 120 Vac, 10 full load amperes (FLA),   
    60 locked rotor amperes (LRA) 
  Valve: 120 Vac, 1A 
  Igniter: 120 Vac, 3A 
  Low Voltage Shutdown: 80 Vac
Environmental Ratings: 
Operating/Shipping Temperature: -40°F to 
     +150°F (-40°C to +66°C). 
Display text may not be visible below -4°F (-20°C) 
Humidity: 0% to 95% relative humidity at 104°F 
     (40°C) noncondensing.