TECHNICIAN’S QUICK REFERENCE GUIDE
69-2500-01
R7284 Series
Electronic Oil Primary
The following service procedures will help you become familiar
with the R7284 electronic oil primary controls. For control
operation, please refer to the basic control functions described on
the back. For further information, wiring instructions and
troubleshooting, please refer to the R7284 Installation Instructions,
form number 69-2467.
Pump Priming Cycle
To facilitate purging air from the oil lines and filters, the R7284 can
be placed in a purge routine by pressing and releasing the up
arrow button during the Trial For Ignition.
In the advanced interface “PUMP PRIME” is displayed on the
display along with the time left on the Trial for Ignition (TFI).
Pressing the up arrow button adds a minute to the TFI time for a
maximum of 10 additional minutes (press the up arrow button 10
times). Pressing the down arrow button subtracts a minute from
the TFI time.
There is no visual indication for the basic interface control and the
purge timing is limited to five minutes.
Home Screens (Advanced Interface)
Pressing the “i” button longer than 2 seconds in states other than
Standby Interrupts control operation.
Once the held key is released a 3 second count down begins to
restart the cycle if the call for heat is still present.
Holding all 3 buttons longer than 2 seconds in any state puts
the display in the Installer Setup (ISU) mode.
Pressing “i” in any state enters the Diagnostic screen if
diagnostics are enabled outside of the Installer Setup mode.
Pressing up or down in any screen enters Error History if
diagnostics are enabled outside of the Installer Setup mode.
Question and Answer IconNeed help?

Do you have a question about the Honeywell R7284 Series and is the answer not in the manual?

Honeywell R7284 Series Specifications

General IconGeneral
TypeOil Primary Control
Frequency50/60 Hz
MountingPanel or surface mount
Switch ActionSPDT
Ignition TypeIntermittent
Voltage120V AC
Operating Temperature Range-40°F to 150°F (-40°C to 65°C)
DisplayLED
Flame Failure Response Time (FFRT)0.8 seconds
LockoutManual reset
ApprovalsUL, CSA
Voltage Rating120V AC

Summary

Technicians Quick Reference Guide

Pump Priming Cycle

Facilitates purging air from oil lines and filters via a purge routine.

Home Screen Interactions (Advanced Interface)

Describes interactions with the advanced interface home screens and button functions.

Lockout Conditions and Recovery

Soft Lockout

Control recovers from Soft Lockout when the error clears or after a set time.

Hard Lockout

Control is in Hard Lockout; reset by holding the "i" button for at least 2 seconds.

Hard Lockout Call Service

Returns to Standby from Hard Lockout by holding the "i" button for over 10 seconds.

Installer Setup Procedures (Advanced Interface)

Entering Installer Setup

Enter Installer Setup by pressing all three buttons simultaneously for 2 seconds.

Installer Setup Options

Options to QUIT (re-baseline) or CONTINUE into Installer Setup.

Advanced Interface Configuration Options

Parameter Adjustments

Adjustments for Valve On Delay, Ignition Time, and Burner Off Delay.

System Configuration

Configure TT terminals, spark control, appliance type, and allowed resets.

Diagnostics and Setup Exit

Enable diagnostics, error history, and exit installer setup.

Error History Screens (Advanced Interface)

Error History Navigation (Advanced Interface)

Basic User Interface Overview

R7284 Status (Basic Interface) LED Codes

R7284 Flame Strength (Basic Interface)

Error History (Basic Interface) Interpretation