Table 7 Canadian Standards Association (CSA)
Code Description
2J
Explosion Proof for Class I, Division 1, Groups B, C & D. Dust-
Ignition-Proof for Class II, Division 1, Groups E, F & G; Class III,
Division 1. Conduit seals not required. 42 Vdc max.
Intrinsically Safe for Class I, Groups A, B, C & D; Class II, Groups E,
F & G; Class III, Divisions 1, T4 at 40°C, T3A at 93°C maximum
ambient. Install per Honeywell drawing 51204242.
Suitable for Class I, II & III, Division 2, Groups A, B, C, D, E, F & G
hazardous locations, T4 at 93°C. 42 Vdc max.
Environmental: Indoor and outdoor hazardous locations
(Encl 4X).
CSA Certified Barriers
(1)
Class I, II, III, Division 1 and 2, Groups
28V / 200 Ω
A - G
20V / 150 Ω
C - G
(1)
Install in accordance with Honeywell drawing 51204242.