What to do if the analog output is incorrect on Honeywell SC?
- UutranJul 28, 2025
To address an incorrect analog output on your Honeywell Measuring Instruments, first, verify the type of analog output (voltage or current) that the channel uses. You can use the DIAGNOSTICS -> DAC FULL SCALE and DIAGNOSTICS -> DAC ZERO SCALE menu items to force the Analog Output to a known output. Then, adjust your readout device, panel meter, PLC, or data acquisition system to match. Also, check the output selection jumpers.