S05, S10, S20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
63-2607—08 10
Fig. 16. Wiring for two-wire SPST on/off control.
Fig. 17. Wiring for floating control.
Fig. 18. Wiring for 0/2-10 Vdc proportioning controllers.
Fig. 19. Wiring for 4-20 mA proportioning controllers.
Fig. 20. Wiring for high side (triac source) floating control.
Fig. 21. Wiring for low side (triac sink) floating control.
ACTUATOR
SPST
24 VAC
1
1
2
3
2
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
V
OR +
OR N/A
FEEDBACK
5
4
3
1
2
M22291A
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
4
24 VAC
1
1
2
3
2
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO FLOATING.
M19573B
ACTUATOR
V
OR +
OR N/A
FEEDBACK
5
4
3
1
2
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
4
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
ACTUATOR
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
2
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
V
OR +
OR N/A
FEEDBACK
+
FEEDBACK
5
4
3
1
2
M19574B
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
4
ACTUATOR
4 TO 20 mA
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
2
490 TO 510
OHMS,
1/2 W
MINIMUM
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
V
OR +
OR N/A
FEEDBACK
+
FEEDBACK
5
4
3
1
2
M22282B
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
4
ACTUATOR
CONTROLLER
24 VAC
1
1
2
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
SET SWITCH TO FLOATING.
V
OR +
OR N/A
FEEDBACK
HOT
COM
5
4
3
1
2
M22283A
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
2
3
3
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
ACTUATOR
CONTROLLER
24 VAC
1
1
2
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
SET SWITCH TO FLOATING.
V
OR +
OR N/A
FEEDBACK
HOT
COM
5
4
3
1
2
M22284A
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
2
3
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
3

Other manuals for Honeywell S05 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell S05 Series and is the answer not in the manual?

Honeywell S05 Series Specifications

General IconGeneral
BrandHoneywell
ModelS05 Series
CategoryController
LanguageEnglish

Related product manuals