EasyManuals Logo
Home>Honeywell>Controller>S05 Series

Honeywell S05 Series User Manual

Honeywell S05 Series
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
S05, S10, S20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
11 63-2607—08
Fig. 22. Wiring for low side (triac sink) floating control
using separate transformers.
Fig. 23. Wiring for 0/2-10 Vdc proportioning controller
operating multiple actuators.
Fig. 24. Wiring for 4-20 mA proportioning controller
operating multiple actuators.
Fig. 25. Wiring for 0/2-10 Vdc proportioning controller
operating multiple actuators as master/drone.
ACTUATOR
CONTROLLER
24 VAC
1
1
2
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
SET SWITCH TO FLOATING.
V
OR +
OR N/A
FEEDBACK
HOT
COM
5
4
3
1
2
M22285A
24 VAC
1
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
2
3
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
3
ACTUATOR
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
2
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
V
OR +
OR N/A
FEEDBACK
+
FEEDBACK
5
4
3
1
2
M19575B
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
ACTUATOR
V
OR +
OR N/A
FEEDBACK
5
4
3
1
2
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
4
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
ACTUATOR
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
4
4
2
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
LOCATE RESISTOR AT THE LAST
ACTUATOR.
V
OR +
OR N/A
FEEDBACK
+
FEEDBACK
5
4
3
1
2
M22286A
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
ACTUATOR
V
OR +
OR N/A
FEEDBACK
5
4
3
1
2
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
500
OHMS
5
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
5
ACTUATOR
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
24 VAC
1
1
2
3
2
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
V
OR +
OR N/A
FEEDBACK
+
FEEDBACK
5
4
3
1
2
M22287A
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
ACTUATOR
V
OR +
OR N/A
FEEDBACK
5
4
3
1
2
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
4
ENSURE PROPER GROUNDING OF ACTUATOR CASE.
4

Other manuals for Honeywell S05 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell S05 Series and is the answer not in the manual?

Honeywell S05 Series Specifications

General IconGeneral
BrandHoneywell
ModelS05 Series
CategoryController
LanguageEnglish

Related product manuals